作者姓名:HOSSEINI  Mehdi  SHAYANFAR  Heidar  Ali  FOTUHI-FIRUZABAD  Mahmud
作者单位:[1]Center of Excellence for Power System Automation and Operation, Department of Electrical Engineering, lran UniversiO, of Science & Technology, Narmak 16846-13114, Tehran, lran [2]Department of Electrical Engineering, Sharif University of Technology, Azadi Ave. 11365-9363, Tehran, lran [3]Technical Engineering of Babol, University, of Mazandaran, Shariati Ave. 47144, P. O. Box 484, Babol, lran
摘    要:This paper presents modeling of Distribution STATCOM (D-STATCOM) in load flow calculations for the steady- state voltage compensation. An accurate model for D-STATCOM is derived to use in load flow calculations. The rating of this device as well as the direction of required reactive power injection for voltage compensation in the desired value (1 p.u.) is de- rived and discussed analytically and mathematically by the phasor diagram method. Furthermore, an efficient method for node and line identification used in load flow calculations is presented. The validity of the proposed model is examined by using two standard distribution systems consisting of 33 and 69 nodes, respectively. The best location of D-STATCOM for under voltage problem mitigation approach in the distribution networks is determined. The results validate the proposed model for D- STATCOM in large distribution systems.

关 键 词:分布系统  电压补偿  负荷跟踪  电工技术
收稿时间:2007-05-21
修稿时间:2007-07-09

Modeling of D-STATCOM in distribution systems load flow
HOSSEINI Mehdi SHAYANFAR Heidar Ali FOTUHI-FIRUZABAD Mahmud.Modeling of D-STATCOM in distribution systems load flow[J].Journal of Zhejiang University Science,2007,8(10):1532-1542.
Authors:Hosseini Mehdi  Shayanfar Heidar Ali  Fotuhi-Firuzabad Mahmud
Institution:(1) Center of Excellence for Power System Automation and Operation, Department of Electrical Engineering, Iran University of Science & Technology, Narmak, 16846-13114 Tehran, Iran;(2) Department of Electrical Engineering, Sharif University of Technology, Azadi Ave., 11365-9363 Tehran, Iran;(3) Technical Engineering of Babol, University of Mazandaran, Shariati Ave., 47144, P.O. Box 484, Babol, Iran
Abstract:This paper presents modeling of Distribution STATCOM (D-STATCOM) in load flow calculations for the steady- state voltage compensation. An accurate model for D-STATCOM is derived to use in load flow calculations. The rating of this device as well as the direction of required reactive power injection for voltage compensation in the desired value (1 p.u.) is de- rived and discussed analytically and mathematically by the phasor diagram method. Furthermore, an efficient method for node and line identification used in load flow calculations is presented. The validity of the proposed model is examined by using two standard distribution systems consisting of 33 and 69 nodes, respectively. The best location of D-STATCOM for under voltage problem mitigation approach in the distribution networks is determined. The results validate the proposed model for D- STATCOM in large distribution systems.