HFC125跨临界热泵热水器性能实验研究
引用本文:王方,连之伟,范晓伟,王凤坤.HFC125跨临界热泵热水器性能实验研究[J].东南大学学报,2010,26(2):182-186.
作者姓名:王方  连之伟  范晓伟  王凤坤
作者单位:王方,连之伟(上海交通大学机械与动力工程学院,上海,200240;中原工学院能源与环境学院,郑州,450007);范晓伟,王凤坤(中原工学院能源与环境学院,郑州,450007) 
基金项目:The National Natural Science Foundation of China(No.50676059)
摘    要:为深入了解HFC125跨临界循环热泵热水器的运行特性,设计和建造了一个直流变频热泵热水器实验装置,对HFC125跨临界循环热泵热水器性能进行了实验研究,发现压缩机运行在95Hz时系统存在一个COP峰值.然后以95Hz为例,研究了系统COP与压缩机频率、冷凝压力、蒸发压力、冷却水温升、压缩机排气温度等参数的关系,并与R410A亚临界循环系统性能进行了比较.结果表明:系统存在一最优频率,此时系统有较好的COP值,系统COP随冷凝压力和压比的降低呈上升趋势,而蒸发压力基本恒定;当冷却水温升超过47.5℃时,COP迅速下降.相对R410A亚临界循环,HFC125跨临界循环系统COP显著提升,提高幅度平均在12%以上.

关 键 词:HFC125  跨临界循环  热泵热水器  COP

Experimental study on characteristics of transcritical heat pump water heater using refrigerant HFC125
Wang Fang, Lian Zhiwei, Fan Xiaowei Wang Fengkun.Experimental study on characteristics of transcritical heat pump water heater using refrigerant HFC125[J].Journal of Southeast University(English Edition),2010,26(2):182-186.
Authors:Wang Fang  Lian Zhiwei  Fan Xiaowei Wang Fengkun
Institution:Wang Fang1,2 Lian Zhiwei1,2 Fan Xiaowei2 Wang Fengkun2(1School of Mechanical Engineering,Shanghai Jiao Tong University,Shanghai 200240,China)(2School of Energy and Environmental Engineering,Zhongyuan University of Technology,Zhengzhou 450007,China)
Abstract:To evaluate the performance of heat pumps using refrigerant HFC125,an experimental rig of a DC-inverter heat pump water heater is designed and set up,and the research on the transcritical heat pump water heater is carried out experimentally.It is found that there is a top value of the coefficient of performance(COP)when the system runs at 95 Hz of frequency.The relationships between the COP and compressor frequency,condensation pressure,evaporation pressure,condensation water temperature rise,and discharge ...
Keywords:HFC125  COP  HFC125  transcritical cycle  heat pump water heater  coefficient of performance(COP)