The modern travelling wave based fault location principles for transmission lines are ana-lyzed. In order to apply the travelling wave principles to HVDC transmission lines, the special tech-nical problems are studied. Based on this, a fault locating system for HVDC transmission lines is developed. The system can support modern double ended and single ended travelling wave princi-ples simultaneously, and it is composed of three different parts: travelling wave data acquisition and processing system, communication network and PC based master station. In the system, the fault generated transients are induced from the ground leads of the over-voltage suppression ca-pacitors of an HVDC line through specially developed travelling wave couplers.The system was applied to 500 Kv Gezhouba-Nanqiao(Shanghai)HVDC transmission line in China. Some field op- eration experiences are summarized, showing that the system has very high reliability and accu- racy,and the maximum location error is about 3 km(not more than 0.3% of the total line length). Obviously, the application of the system is successful, and the fault location problem has finally been solved completely since the line operation. 相似文献